Home>Product>Split Core Current Transformer >FU-80 Low Cost Indoor Single Phase Split Core Current Transformer 1000/5a

FU-80 LOW COST INDOOR SINGLE PHASE SPLIT CORE CURRENT TRANSFORMER 1000/5A

fu-80_low_cost_current_transformer

INTRODUCE

The model FU-80 is a split-core current transformer offers 333mV, 100mV-2V and 10mA-500mA, 1A or 5A at secondary from sensed primary current (0-1200A). This model has three diameter version (30mm, 55mm and 80mm), suite for all kinds of customers application.
This model FU-80 ct is a economic split core current transformer, using ABS and Anti-fire cover, it is very easy for installation.It has Low phase shift for power measurement. Length of the output lead can be customized. This current transformer is compact and low cost current transformer with high accuracy. The CTs are ideal for quick and easy installation without disconnecting cables during installation. Multiple installation mechanisms provide stable and durable current measurement.
All of our split core current transformers are strictly comply IEC60044-1, IEC61869-2, ANSI/IEEE C57.13, NTC 2205, GB1208-2006, GB/T 20840.1-2010, GB/T 20840.2-2014, GB/T 22071.1-2018.

FEATURES

Measurement range of 1mA to 1200A AC; High accuracy 0.2%, 0.5s, 0.5%; Holding wire diameter: φ30mm or φ55mm or φ80mm; Most cost-effective; Faster installation; Low cost deign; Safe and easy installations; Low phase shift for power measurement; Isolated plastic case recognized according to UL94-V0; Small-size, compact size, light-weight; Over-Voltage protection circuit is installed; CE, UL/EN 61010-1 certified;

APPLIATIONS

HEMS(home energy management system); BEMS(building energy management system); Various power monitoring systems; Sub-metering accurate measurement; Power quality analyzer meter; Energy meter current measurement; Smart grid application features; Three phase balance control; Distribution boxes Load center; Digital fault recorders; In-factory display In-home display; Inverters for solar & wind turbine systems; Power measurement device for PLC; Data loggers to analyze building & machinery performance;

WIRING DIAGRAMS

P1, P2 is primary polarity terminal, S1, S2 is secondary polarity terminal.
P2, S2 is homonymous terminals (subtractive polarity).

PARAMETERS

Electrical parameters 
Standards IEC60044-1; IEC 61869-2; NTC 2205; ANSI/IEEE C57.13; GB1208-2006; GB/T 20840.1-2010; GB/T 20840.2-2014; GB/T 22071.1-2018; IEC61010-1
Ratio 100:1, 400:5, 1000:5 or 1000:1 etc, customized
Accuracy 0.2, 0.5, 1
Range of primary rated current 100A/150A/200A/250A/300A/400A/500A/600A/750A/800A/1000A/1200A
Range of rated burden 2.5VA-5VA
Rated frequency 50/60Hz
Rated secondary output 50mA-500mA, 1A, 5A AC optional
333mV AC or 100mV-2V optional
Frequency range 40Hz-2KHz
System voltage 720V(0.72kV)
Rated continuous thermal current 120%I1n continuously
Secondary winding power frequency withstand voltage (dielectric strength) 3kV, 1min
Safety CAT IV 600V IEC/EN 61010-1
Output K1, K2 or S1, S2
Protection level 3.0V0-P
Internal structure Clamp-on design
Installation and fixation method Ribbon
Material Silicon steel sheets+enameled wire+ABS+ 94V-0
Mechanical parameters
Dimensions (W×D×H) (mm) 88 x 129 x 28, 108 x 155 x 28, 138 x 193 x 28
Jaw cable diameter(mm) 30mm, 55mm, 80mm
Weight (kg) 400, 550, 600
Color Black
Working conditions  
Operating temperature -25°C to +55°C
Storage temperature -40°C to +70°C
Environment Indoors
Altitude <3000 meters
Conditions No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

TECHNICAL DATA

Type FU-30, FU-55, FU-80
Purpose Measuring current transformer
Ratio Accuracy class
I1/I2 0.2 0.5 1
5A/333mV YES YES YES
10A/333mV YES YES YES
20A/333mV YES YES YES
50A/333mV YES YES YES
60A/333mV YES YES YES
100A/333mV YES YES YES
150A/333mV YES YES YES
200A/333mV YES YES YES
300A/333mV YES YES YES
400A/333mV YES YES YES
500A/333mV YES YES YES
600A/333mV YES YES YES
750A/333mV YES YES YES
800A/333mV YES YES YES
1000A/333mV YES YES YES
10A/5mA YES YES YES
20A/10mA YES YES YES
50A/25mA YES YES YES
60A/30mA YES YES YES
100A/50mA YES YES YES
150A/75mA YES YES YES
200A/100mA YES YES YES
50A/50mA YES YES YES
60A/60mA YES YES YES
100A/100mA YES YES YES
150A/150mA YES YES YES
200A/200mA YES YES YES
100A/100mV YES YES YES
100A/1V YES YES YES
100A/2V YES YES YES
100A/5V YES YES YES
100A/10V YES YES YES
200A/1V YES YES YES
200A/2V YES YES YES
200A/5V YES YES YES
200A/10V YES YES YES
100A/1A YES YES YES
200A/1A YES YES YES
300A/1A YES YES YES
400A/1A YES YES YES
500A/1A YES YES YES
600A/1A YES YES YES
800A/1A YES YES YES
1000A/1A YES YES YES
200A/5A YES YES
300A/5A YES YES
400A/5A YES YES
500A/5A YES YES
600A/5A YES YES
700A/5A YES YES
750A/5A YES YES
800A/5A YES YES
1000A/5A YES YES
1200A/5A YES YES

SELECTION GUIDE

Model Primary rated current Rated load Secondary output Aperture (mm) Description (mm) Weight (kg)
FU-16 5-200A ≤10Ohm 333mV,1V, 5V,100mA φ16 38 x 55 x 18 0.06
FU-32 100-600A ≤10VA 333mV,1V, 5V, 1A, 5A φ32 110 x 130 x 41 0.7
FU-36 100-600A ≤2.5VA 333mV,1V, 5V, 1A, 5A φ10, φ16, φ24, φ36 26 × 43 × 27
31 × 50 × 30
43 ×73 × 39
60 × 89 × 43
0.1,
0.12,
0.2,
0.35
FU-80 100-1200A ≤5VA 333mV,1V, 5V, 1A, 5A φ30, φ55, φ80 88 x 129 x 28
108 x 155 x 28
138 x 193 x 28
0.4, 0.55, 0.6
FU-100 300-3000A ≤10VA 333mV,1V, 5V, 1A, 5A φ100 170 x 184.5 x 41 1
FU120 200-4000A ≤10VA 333mV,1V, 5V, 1A, 5A 120 x 130, 120 x 30 166 x 110 x 49
166 x 208 x 49
1.2, 1.7
FU160 500-5000A ≤20VA 333mV,1V, 2V, 5V,1A, 5A 160 x 80, 120 x 80 144 x 227 x 54 2.8, 2.3

ORDERING INFORMATION

Be sure to the type, current ratio, accuracy class, rated load and use of the products when you plan to make a order. Special specifications could be customized. All kinds of different specifications and parameters current transformers can be made according to your needs.