Home>Product>Current Transformer>Medium Voltage Current Transformer >LZCG2500-10 Medium Voltage 100/5a Protection Zct Zero Sequence Current Transformer 5P20

LZCG2500-10 MEDIUM VOLTAGE 100/5A PROTECTION ZCT ZERO SEQUENCE CURRENT TRANSFORMER 5P20

lzcg2500-10_zero_sequence_current_transformer_5p20

INTRODUCE

The Model LZCG2500-10 ZCT is a ring type resin casting zero sequence current transformer. Some clients also called it as zero phase current transformer & TTCC. This current transformer can be used both for measurement and microcomputer protection of electrical equipment in 11KV and 35KV AC power system such as ABB-Safe Ring/Safe plus...and cable distribution boxes.
We used imported silicon material and using our mature advanced producing technology we make sure our transformer has very good linear and more than 20 years using life in order to be qualified with all the jobs. The ring core and secondary windings are vacuum poured by high quality epoxide insulated resin ,which has the characteristic of moisture proof, stable performance and dispensing with maintenance. Current transformer protection class 5P20, 5P10, 10P20, 10P10, 10P5.
All of our GFUVE zero sequence current transformers are strictly comply IEC60044-1, IEC 61869-2, ANSI/IEEE C57.13, GB1208-2006, GB/T 20840.1-2010, GB/T20840.2-2014, GB/T 22071.1-2018, IEC/EN61010-2-032, IEC/EN 61010-2-031.

FEATURES

Protection class 5P20, 5P10, 10P15, 10P10, 10P5; 50/5A, 100/5A, 200/5A, 300/5A, 400/5A, 500/5A, 600/5A, 800/5A, 1000/5A... 100/1A, 200/1A, 300/1A, 400/1A, 500/1A, 600/1A, 750/1A, 800/1A, 1000/1A... IEC60044-1, IEC/EN 61869-2, NTC 2205, GB/T 20840.2-2014, ANSI/IEEE C57.13; Accuracy class 0.5s, 0.5%, 1; Measurement range 0-3000A AC; Holding wire diameter: φ120mm, φ140mm, φ160mm; Size: φ120xφ185x100, φ140xφ210x100, φ160xφ250x80; Secondary windings are vacuum poured by insulated resin; As a measurement and protection current transformer; High magnetic conductivity silicon steel material; Using life more than 20 years; Easily installation, with mounting bracket; Support dual ratio; Polyurethane resin casting; The protection level CT can accept customized design; As protection CT & measurement CT;

APPLIATIONS

Protective relay device; Ring network cabinet; MV switchgears; Air switch cabinet; Distribution boxes; Three phase power transformer; Medium voltage metering system; Low voltage metering system; Distribution power transformer monitor system; Power quality meter; Measuring instrument; Energy meter; Power meter; Meter tester; Current load monitoring;

WIRING DIAGRAMS

P1, P2 is primary polarity terminal, S1, S2 is secondary polarity terminal.
P2, S2 is homonymous terminals (subtractive polarity).

PARAMETERS

Electrical parameters 
Standards IEC60044-1; IEC 61869-2; NTC 2205; ANSI/IEEE C57.13; GB1208-2006; GB/T 20840.1-2010, GB/T 20840.2-2014, GB/T 22071.1-2018
Accuracy class 0.2S, 0.2, 0.5S, 0.5, 1 (IEC61869-2 standard)
5P20, 5P10, 10P10, 10P15, 10P5
Rated primary current 50-3000A
Rated load ≤30VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Ratio 50/5A, 100/5A, 150/5A, 200/5A, 300/5A, 400/5A, 500/5A, 1000/5A...3000/5A
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS ≤10
Insulation class E
Material Polyurethane+silicon steel sheets+Enameled wire+ABS
Mechanical parameters  
Dimensions (W×D×H) (mm) φ120xφ185x100, φ140xφ210x100, φ160xφ250x80
Jaw cable diameter(mm) 120, 140, 160
Weight (kg) 7, 8, 9
Operating conditions  
Operating temperature -40°C to +70°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Environment Indoors
Altitude <3500 meters
Conditions No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

TECHNICAL DATA

Type LZCG2500-10
Purpose Measuring current transformer Protection current transformer Double winding current transformer
Ratio Accuracy class and rated load(VA) Accuracy class and rated load(VA) Composite accuracy class and rated load (VA)
I1/I2 0.2 0.5 1 3 5P20 10P15 10P10 10P5 0.5 1 10P10 10P5
100/1 2 2.5 5 2.5 2 2.5 5 2 2.5 1.5 2
200/1 2 2.5 5 2.5 3 5 7.5 2.5 2.5 2 2
300/1 2.5 3.75 5 2.5 3 5 7.5 3.75 3.75 2.5 2.5
400/1 2.5 5 10 2.5 3 5 10 5 5 2.5 2.5
500/1 2.5 5 10 3.75 6.25 10 5 5 2.5 2.5
600/1 5 7.5 10 5 7.5 10 5 5 5 5
750/1 2.5 5 7.5 10 5 5 5 5
800/1 2.5 5 10 15 5 5 5 5
1000/1 5 5 10 15 5 5 5 5
1200/1 5 10 15 20 10 10 10 10 15 2.5 5
1500/1 5 10 15 20 10 10 10 10 15 2.5 5
1600/1 10 20 25 30 10 10 10 10 15 2.5 5
2000/1 10 20 25 30 10 10 10 10 15 2.5 5
50/5 2.5 2.5 2
75/5 2.5 2.5 2.5
100/5 2.5 2.5 2.5 2.5 2.5
200/5 2.5 2.5 5 2.5 5 2.5
300/5 5 5 5 2.5 2.5 5 7.5 5 5 2 2.5
400/5 5 5 5 2.5 2.5 5 7.5 5 7.5 2.5 5
500/5 5 7.5 10 5 5 7.5 10 5 7.5 2.5 5
600/5 5 7.5 10 5 5 7.5 10 5 10 2.5 5
750/5 2.5 7.5 10 15 5 5 10 10 7.5 10 2.5 5
800/5 2.5 7.5 10 15 5 5 10 10 7.5 15 2.5 5
1000/5 5 10 15 20 5 10 10 10 10 15 2.5 5
1200/5 5 10 15 20 10 10 10 10 15 2.5 5
1500/5 5 10 15 20 10 10 10 10 15 2.5 5
1600/5 10 20 25 30 10 10 10 10 15 2.5 5
2000/5 10 20 25 30 10 10 10 10 15 2.5 5
2500/5 15 20 25 30 10 10 10 10 15 2.5 5
3000/5 15 20 25 30 10 10 10 10 15 2.5 5

SELECTION GUIDE

Model Primary rated current Rated load Aperture (mm) Description(mm) Weight (kg)
LZCK310-10 300-1000A ≤10VA φ50 φ50 x φ110 x 32 1
LZCK322-10 30-1000A ≤10VA φ50 φ50 x φ110 x 52 1.6
LZCK350-10 30-1000A ≤25VA φ50 φ50 x φ110 x 105 3.1
LZCK720-10 30-1000A ≤25VA φ80 φ80 x φ110 x 50 2.1
LZCK2500-10 30-3000A ≤30VA φ120,140,160 φ120 x φ185 x 100 7
LZCG530-10 30-1000A ≤20VA φ45 φ45 x φ120 x 65 2.1
LZCG930-10 30-1500A ≤25VA φ60 φ60 x φ155 x 60 3.6
LZCT722-10 30-1500A ≤10VA φ82 φ82 x φ130 x 55 2.3
LZCG2500-10 30-3000A ≤30VA φ120,140,160 φ120 x φ185 x 100 7

ORDERING INFORMATION

Be sure to the type, current ratio, accuracy class, rated load and use of the products when you plan to make a order. Special specifications could be customized. All kinds of different specifications and parameters current transformers can be made according to your needs.