Home>Product>Zero Sequence Current Transformer>LZCT722-10 100/1a Medium Voltage 5p10 Protection Zero Sequence Current Transformer Zct

LZCT722-10 100/1A MEDIUM VOLTAGE 5P10 PROTECTION ZERO SEQUENCE CURRENT TRANSFORMER ZCT

lzct722-10_zct_zero_sequence_current_transformer

INTRODUCE

LZCT722-10 zero sequence current transformer is suitable for current measurement and microcomputer protection of electrical equipment in 10KV and 35KV AC power system. It is not only widely used in compact fully insulated ring net switch cabinets and load switch cabinet but also cable distribution boxes because of its small size, light weight, open feasibility and convenient. It is very convenient that the transformer can be directly installed at connected output and input cables.
New magnetic material amorphous alloy or permalloy is taken to be the core of the bushing type current transformer, which has high magnetic permeability, low saturation induction density and good stability. Therefore, the measuring accuracy is higher and the instrument security factor in lower. Since the high quality silicon steel sheet metal processed by advanced technology is taken to be the core of the protection windings, the accuracy limit factor will be higher.
The circular ring core and secondary windings are poured by quality epoxies resin or polyurethane or silicon rubber in the fire retardant plastic casing, which has the characteristic of moisture proof, stable performance and dispensing with maintenance. The cable can cross the window type current transformer through its internal poles quickly and uniformly.
All of our GFUVE zero sequence current transformers are strictly comply IEC60044-1, IEC61869-2, ANSI/IEEE C57.13, GB1208-2006, GB/T 20840.1-2010, GB/T20840.2-2014, GB/T 22071.1-2018, IEC/EN61010-2-032, IEC/EN61010-2-031.

FEATURES

Accuracy class 0.2s, 0.2, 0.5s, 0.5, 1; Protection class 5P20, 5P10, 10P15, 10P10, 10P5; Measurement range 0-1500A AC; Holding wire diameter: φ82mm; Size: φ82xφ130x55; IEC60044-1, IEC/EN61869-2, NTC 2205, GB/T 20840.2-2014, ANSI/IEEE C57.13; Secondary windings are vacuum poured by insulated resin; As a measurement and protection current transformer; High magnetic conductivity silicon steel material; Using life more than 20 years; Easily installation, with mounting bracket; Support dual ratio; Polyurethane resin casting; The protection level CT can accept customized design; 50/5A, 100/5A, 200/5A, 300/5A, 400/5A, 500/5A, 600/5A, 1000/5A...1500/5A; 100/1A, 200/1A, 300/1A, 400/1A, 500/1A, 600/1A, 800/1A, 1000/1A...1500/1A;

APPLIATIONS

Protective relay device; Three phase power transformer; Medium voltage metering system; Low voltage metering system; MV switchgears; Ring network cabinet; Air switch cabinet; Distribution boxes; Power quality meter; Measuring instrument; Energy meter; Power meter; Meter tester; Current load monitoring; Distribution power transformer monitor system;

OUTLINE DRAWING

WIRING DIAGRAMS

P1, P2 is primary polarity terminal, S1, S2 is secondary polarity terminal.
P2, S2 is homonymous terminals (subtractive polarity).

PARAMETERS

Electrical parameters 
Standards IEC60044-1; IEC 61869-2; NTC 2205; ANSI/IEEE C57.13; GB1208-2006; GB/T 20840.1-2010; GB/T 20840.2-2014; GB/T 22071.1-2018
Accuracy Class 0.2S, 0.2, 0.5S, 0.5, 1 (IEC61869-2 standard)
5P20, 5P10, 10P10, 10P15, 10P5
Rated primary current 50-1500A
Rated load ≤20VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Ratio 50/5A, 100/5A, 150/5A, 200/5A, 300/5A, 400/5A, 500/5A...1500/5A; 100/1A, 200/1A...1500/1A;
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS≤10
Insulation Class E
Material Polyurethane+Silicon steel sheets+Enameled wire+ABS
Mechanical parameters  
Dimensions (W×D×H) (mm) φ82 x φ130 x 55
Jaw cable diameter(mm) 82
Weight (kg) 2.3
Operating conditions  
Operating temperature -40°C to +70°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Environment Indoors
Altitude <3500 meters
Conditions No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

TECHNICAL DATA

Type LZCT720-10
Purpose Measuring current transformer Protection current transformer Double winding current transformer
Ratio Accuracy class and rated load(VA) Accuracy class and rated load(VA) Composite accuracy class and rated load (VA)
I1/I2 0.2S 0.2 0.5 10P15 10P10 10P5 0.5 1 10P10 10P5
50/1 2 0.75 2 1.5 0.6
100/1 3.75 1 1.5 2 2.5 0.75 1.5
200/1 2.5 5 1.25 2 3 1 2
300/1 2.5 3.75 5 1.5 2.5 3.75 1.5 3
400/1 3.75 5 7.5 1.5 3 5 1.5 3
500/1 5 7.5 10 2 3.5 5 1.5 3
600/1 7.5 10 15 2 3.75 7.5 1.5 3
750/1 7.5 10 15
800/1 7.5 10 15
1000/1 7.5 10 15
1200/1 10 10 20
1500/1 10 10 20
75/5 2.5 2.5
100/5 3.75 3.75
200/5 3.75 3.75 2.5 6.25 3.75 2.5
300/5 3.75 5 10 2.5 5 5 2.5 5
400/5 5 7.5 15 2.5 5 7.5 3.75 6.25
500/5 7.5 10 15 3.75 5 7.5 3.75 6.25
600/5 7.5 10 20 3.75 5 10 5 7.5
750/5 7.5 10 20
800/5 10 15 20
1000/5 10 15 25
1200/5 15 15 25
1500/5 15 15 25

SELECTION GUIDE

Model Primary rated current Rated load Aperture (mm) Description(mm) Weight (kg)
LZCK310-10 300-1000A ≤10VA φ50 φ50 x φ110 x 32 1
LZCK322-10 30-1000A ≤10VA φ50 φ50 x φ110 x 52 1.6
LZCK350-10 30-1000A ≤25VA φ50 φ50 x φ110 x 105 3.1
LZCK720-10 30-1000A ≤25VA φ80 φ80 x φ110 x 50 2.1
LZCK2500-10 30-3000A ≤30VA φ120,140,160 φ120 x φ185 x 100 7
LZCG530-10 30-1000A ≤20VA φ45 φ45 x φ120 x 65 2.1
LZCG930-10 30-1500A ≤25VA φ60 φ60 x φ155 x 60 3.6
LZCT722-10 30-1500A ≤10VA φ82 φ82 x φ130 x 55 2.3
LZCG2500-10 30-3000A ≤30VA φ120,140,160 φ120 x φ185 x 100 7

ORDERING INFORMATION

Be sure to the type, current ratio, accuracy class, rated load and use of the products when you plan to make a order. Special specifications could be customized. All kinds of different specifications and parameters current transformers can be made according to your needs.