Home>Product>Low Voltage Current Transformer>FU-100II 1000a 2000a 3000a 4000a Window Busbar Type Low Voltage Current Transformer

FU-100II 1000A 2000A 3000A 4000A WINDOW BUSBAR TYPE LOW VOLTAGE CURRENT TRANSFORMER

fu-100ii_4000a_window_busbar_type_current_transformer

INTRODUCE

FU-100II economic low voltage current transformer is low cost ac busbar type current transformer, measuring AC current from 500A to 4000Amps passing through the center conductor. This model has three version (class 0.2, 0.5, 1), suite for all kinds of electrical customers application. LV current transformers are intended for supplying measuring instruments and protection circuits of electrical power devices with a maximum operating voltage of 0.72kV and frequency of 50Hz or 60Hz after prior arrangement with the manufacturer of GFUVE GROUP. LV current transformers are supplied with accessories which help to install and secondary terminal cover with possibility of sealing. 
All of our GFUVE low voltage busbar type current transformers are strictly comply IEC60044-1, IEC61869-2, ANSI/IEEE C57.13, GB1208-2006, GB/T 20840.1-2010, GB/T 20840.2-2014, GB/T 22071.1-2018, IEC/EN61010-2-032, IEC/EN 61010-2-031, IEC60185, JJG1021.

FEATURES

Measurement range of 500A to 4000A AC; Holding wire diameter: Φ100*50mm; Low phase shift for power measurement; Small-size, compact size, light-weight; Most cost-effective; Using high magnetic silicon steel, good linearity and high sensitivity; Burden from 2.5VA to 30VA; IEC60044-1, IEC61869-2, ANSI/IEEE C57.13, IEC60185 standard; Isolated plastic case recognized according to UL94-V0; Current, electrical energy measurement in 50Hz/60Hz A.C. circuits; Rated voltage≤0.72kV; Design using for more than 15years; Safe and easy installation to distribution panels; Accuracy class 0.2, 0.5, 1; CE, UL/EN 61010-1 certified;

APPLIATIONS

HEMS(home energy management system); BEMS(building energy management system); Various power monitoring systems; Sub-metering accurate measurement; Smart grid application features; Three phase balance control; Energy meter; Power quality meter; Energy meter current measurement; Protection relay; Load center; Digital fault recorders; In-factory display In-home display; Inverters for solar & wind turbine systems; Power measurement device for PLC; Data loggers to analyze building & machinery performance;

PARAMETERS

Electrical parameters 
Standards IEC60044-1; IEC61869-2; NTC 2205; ANSI/IEEE C57.13; GB1208-2006; GB/T 20840.1-2010; GB/T 20840.2-2014; GB/T 22071.1-2018; IEC60185; JJG1021;
Model FU-100II
Type Indoor type
Rated system voltage, kV 0.38, 0.22
Highest system voltage, kV <0.72
Fault current of system, KA 40KA / 3Sec
Accuracy class 0.2, 0.5, 1(IEC60044-1/IEC61869-2 standard)
Rated primary current 1000A, 1500A, 2000A, 2500A, 3000A, 4000A;(500-4000A)
Rated load 2.5VA - 30VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Ratio 500/5A, 1000/5A, 1500/5A, 2000/5A, 2500/5A, 3000/5A, 4000A/5A, 500/1A, 1000/1A, 1500/1A, 2000/1A, 2500/1A, 3000/1A, 4000A/1A or customized
Rated short-time thermal current 25kA, 1S
Rated continuous thermal current 120%I1n
Dielectric strength 3KV 50Hz/60Hz at 1 minute
Instrument security factor FS≤10
Output mode Terminal output
Material of insulation Dry type, ABS
Mechanical parameters  
Dimensions((W×D×H)(mm) 166 x 152 x 48
Max. jaw Bus bar(mm) 100 x 50
Max. jaw cable diameter(mm) 50
Weight(g) 1.5
Operating conditions  
Operating temperature -20°C to +55°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Relative humidity 0-85% non-condensing
Environment Indoors
Altitude <3500 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

TECHNICAL DATA

Type FU-100II
Purpose Measuring current transformer Straight through turns
Rated primary current (AMP) Accuracy class and rated load(VA)
0.2 0.5 1
500 5* 10 7.5 1
600 5* 10 15 1
750 5* 10 15 1
800 5* 10 15 1
1000 5* 15 15 1
1250 5* 20 20 1
1500 5* 20 20 1
2000 5* 20 20 1
2500 5* 20 20 1
3000 5* 30 30 1
4000 5* 30 30 1

SELECTION GUIDE

Model Primary rated current Rated load Aperture (mm) Description (mm) Weight (kg)
FU-30II 15-300A ≤10VA φ22 or 30 x 10 60 x 67 x 37 280
FU-40II 100-800A ≤10VA φ31 or 40 x 10 75 x 82 x 40 350
FU-50II 200-800A ≤10VA φ45 or 60 x 20 101 x 110 x 40 500
FU-60II 400-1500A ≤20VA φ32 or 60 x 30 102 x 110 x 48 800
FU-80II 500-2000A ≤20VA φ32 or 80 x 30 121 x 118 x 46 1000
FU-100II 500-4000A ≤20VA φ50 or 100 x 50 166 x 152 x 48 1500

ORDERING INFORMATION

Be sure to the type, current ratio, accuracy class, rated load and use of the products when you plan to make a order. Special specifications could be customized. All kinds of different specifications and parameters current transformers can be made according to your needs.